Cable Voltage Drop Calculator
Determine the minimum cable size required to stay within voltage drop limits. Supports AWG and metric sizes, copper and aluminum, single and three phase.
How to Calculate Cable Size
The formula and steps to find the right wire gauge for your voltage drop requirements.
The Voltage Drop Formula
Where K is the resistivity constant (12.9 for copper, 21.2 for aluminum), I is the current in amps, L is the one-way length in feet, M is the phase multiplier (2 for single-phase, 1.732 for three-phase), and CM is the circular mil area of the conductor.
Step by Step
- Calculate max allowed drop: Voltage × (Max Drop % / 100)
- Find required circular mils: (K × I × L × M) / max drop in volts
- Select standard cable: Choose the next larger standard AWG or mm² size
- Verify: Calculate actual voltage drop with the selected cable
Voltage Drop Code Requirements
NEC recommendations for maximum voltage drop in electrical installations.
Branch Circuits
Maximum 3% voltage drop for branch circuits supplying lighting, outlets, and appliances. This is the most common standard.
Feeder Circuits
Maximum 2% voltage drop for feeder conductors. Combined feeder + branch drop should not exceed 5% total.
Critical Equipment
Sensitive electronic equipment may require tighter limits (1-2%). Motor circuits have special starting voltage drop considerations.
Cable Size Chart
Standard AWG and metric cable sizes with circular mil areas.
| AWG | mm² | Circular Mils | Typical Use |
|---|---|---|---|
| 14 | 2.08 | 4,110 | Lighting, outlets (15A) |
| 12 | 3.31 | 6,530 | General purpose (20A) |
| 10 | 5.26 | 10,380 | Appliances, dryers (30A) |
| 8 | 8.37 | 16,510 | Ranges, HVAC (40-50A) |
| 6 | 13.30 | 26,240 | Sub-panels, large loads (55-65A) |
| 4 | 21.15 | 41,740 | Feeders, service entrances (70-85A) |
| 2 | 33.62 | 66,360 | Main feeders, large motors (95-115A) |
| 1 | 42.41 | 83,690 | Service conductors (130A) |
| 1/0 | 53.49 | 105,600 | Large service entrances (150A) |
| 2/0 | 67.43 | 133,100 | Heavy industrial (175A) |
Frequently Asked Questions
Common questions about cable voltage drop calculations.
Use the formula: CM = (K × I × L × M) / VD. K is 12.9 for copper or 21.2 for aluminum. I is current in amps. L is one-way length in feet. M is 2 for single-phase or 1.732 for three-phase. VD is the maximum allowed voltage drop in volts.
The NEC recommends 3% maximum for branch circuits and 5% total for feeder + branch circuits combined. Some local codes may have stricter requirements. For sensitive equipment, 1-2% is often recommended.
Longer cable runs have higher resistance, which causes more voltage to be lost as heat. This is why longer runs require thicker cables — a larger cross-section reduces resistance and keeps voltage drop within acceptable limits.
AWG (American Wire Gauge) is the North American standard. Higher AWG numbers mean thinner wire. mm² is the metric cross-sectional area standard. For example, 10 AWG = 5.26 mm². This calculator shows both for convenience.
Copper has lower resistivity (12.9 vs 21.2 for aluminum), meaning less voltage drop for the same cable size. Copper is preferred for long runs where voltage drop is a concern. Aluminum is lighter and cheaper but requires one to two sizes larger to match copper's performance.